Energy
IE2 / IE3 / IE4 running-cost estimate
Rated kW on the plate is output. Electrical input is output ÷ efficiency. Annual energy is input × hours × load factor. This estimate does not invent IEC efficiency percentages: you type the efficiencies from the two nameplates or from a test report. Compare the same kW, hours and tariff across IE2, IE3 and IE4. It is a project filter, not a guaranteed payback.
About this tool
Rated kW on the plate is output. Electrical input is output ÷ efficiency. Annual energy is input × hours × load factor. This estimate does not invent IEC efficiency percentages: you type the efficiencies from the two nameplates or from a test report. Compare the same kW, hours and tariff across IE2, IE3 and IE4. It is a project filter, not a guaranteed payback.
Who this is for
Use it for energy-policy discussions when you already have (or can assume) efficiency figures.
Calculator
Type efficiencies from the nameplate or test report. Leave IE4 blank if you are only comparing IE2 and IE3. Currency is just a number — same unit on every row.
What the numbers mean
- Rated kW
- Shaft output. Electrical input (kW) = output ÷ (η/100). A 7.5 kW motor at 90% efficiency draws about 8.33 kW from the grid at full load.
- Efficiency η
- Nameplate or test-report percentage at the stated load (usually 100% or 75% of rated). IEC class (IE2/IE3/IE4) is a band, not one number for every kW and pole count. This tool never invents η — type the figure from the two plates you are comparing.
- IE2 / IE3 / IE4
- Efficiency classes in IEC 60034-30-1. Higher class → higher η at the same kW/poles, so less kWh for the same shaft work. Minimum legal class depends on the country and the rating.
- Hours / year
- Running hours. 6000 h is a typical process pump (about 16 h × 365). A fan that runs 2000 h saves less than the same kW on continuous duty.
- Load factor
- Average load ÷ rated load. 0.8 means you treat the motor as 80% loaded all year. It is a filter, not a measured duty cycle.
- Tariff
- Price per kWh in your currency. The table is a number; keep the same currency on every row.
- Annual energy
- kWh/year ≈ (kW_output / η) × hours × load factor. Cost = kWh × tariff. Ignore this as a payback certificate — use it to see if an IE3 upgrade is even in the right order of magnitude.
Worked numbers (you still type η)
Example only, using 7.5 kW, 6000 h, load 0.8, tariff 0.12. Efficiencies below are sample nameplate-style figures so you can see the formula — replace them with your plates.
| Class (example η) | η used | kWh / year | Cost / year (same tariff) |
|---|---|---|---|
| IE2 example | 87% | 41379 | 4966 |
| IE3 example | 90.4% | 39823 | 4779 |
| IE4 example | 92.6% | 38877 | 4665 |
Need a JW motor?
Send kW or hp, volts, frequency, poles, mounting, and a nameplate photo. Stock IEC three-phase (YE3 / Y2) or custom windings — we quote from the plate, not from the logo.